The rule
California adds this section to the plumbing code. It covers earthquake-actuated gas shutoff valves: valves that automatically shut off the gas at the valve location during a seismic disturbance.
The CPC doesn't itself order one for every building. The valves are provided for buildings when installation is required by local ordinance. They have to be certified by the State Architect as conforming to California Code of Regulations, Title 24, Part 12, Chapter 12-16-1.
Valves that aren't certified by the State Architect are prohibited in buildings open to the public where installation is mandatory under local ordinance. The valves are installed in accordance with the local ordinance and, where there's no ordinance, per the manufacturer's installation instructions.
So the answer to 'do I need one?' depends on the local ordinance for your location. Your city or county building department can tell you.
On the job
- Ask the building department whether a local ordinance requires the valve for the type of work you're doing, before you quote it or order one.
- Check the certification before you buy. A valve that isn't State Architect certified is the wrong valve where installation is mandated.
- Keep the manufacturer's installation instructions in the file. If the ordinance doesn't say how to install it, those instructions control.
- Keep this separate from water heater strapping, which is a different seismic rule in Section 507.2.
The inspector and your city's adopted edition have the final word.