The rule
A direct connection between drinking water piping and a drain is never allowed, even if you put a backflow device on it. The only legal way for potable water to reach the drainage system is across open air.
That air gap is two diameters of the supply inlet pipe, and in no case less than 1 inch. So a small supply line still needs the full 1 inch, and a larger supply line needs two of its own diameters.
There's one alternative: connecting to the inlet side of a trap, if an approved vacuum breaker is installed at least 6 inches (or the distance in the device's listing) above the flood-level rim of the trapped fixture, so the device is never under backpressure.
On the job
- Measure the air gap from the bottom of the supply outlet to the flood-level rim of the receptor, not to the top of the drain pipe.
- Equipment with a water makeup line to a floor sink or standpipe is where this shows up most. Check the supply diameter and set the gap from that.
- Many fixtures with an integral air gap are listed for a smaller gap. Install those per their listing, and don't assume the 1 inch number applies to them.
The inspector and your city's adopted edition have the final word.