Home › Guides › Backflow and irrigation

Guide

Backflow prevention for homeowners: irrigation, hose bibbs and annual testing

Any sprinkler system or hose connection can pull dirty water back into your drinking water if the supply pressure drops, so the code requires a backflow device, and a testable assembly needs a test at least once a year.

The short answer

Backflow is water running the wrong way. A main break or a big draw can create a vacuum that pulls used water back up your line (backsiphonage), and a pump or boiler can push harder than the supply does (backpressure). The code says no fixture or equipment may be able to pollute the supply unless an approved device matched to the hazard is provided (CPC 602.3). A sprinkler system with no pump and no chemical injection can use an atmospheric vacuum breaker, a pressure vacuum breaker, a spill-resistant version, an RP assembly or an IAPMO PS 72 valve. A system with a pump or fertilizer injector takes an RP (CPC 603.5.6). Testable assemblies get tested at installation, after repair or moving, and at least once a year (CPC 603.2).

Quick map

  • Hose bibb: built-in nonremovable vacuum breaker
  • Sprinklers, no pump or injector: AVB, PVB, SVB, RP or PS 72 valve
  • Pump, booster or injector: RP
  • Annual test by a certified tester

Backsiphonage and backpressure

The protection depends on the hazard and the direction. A device that stops one direction doesn't always stop the other, which is why Table 603.2 lists both. The simplest protection is a fixture built with open air between the faucet and the flood-level rim (CPC 602.3). Where that can't be guaranteed, you need a device. A direct connection between drinking water and a drain is never allowed. Potable water reaches a drain only across an air gap of two supply pipe diameters, never less than 1 inch (CPC 603.4.4).

The devices, in short

An air gap is open space. An atmospheric vacuum breaker (AVB) is a body with a check and an air port, and it handles backsiphonage only. A pressure vacuum breaker (PVB) adds a loaded air inlet, test cocks and shutoff valves. A double check assembly (DC) has two check valves and handles low hazards in both directions. A reduced-pressure principle assembly (RP) has two checks plus a relief valve, covers both directions and both hazard levels, and is the one chosen for high hazards (CPC 603.3).

Mounting heights matter. An AVB goes upright, open to air, at least 6 inches above the downstream piping and the flood-level rim. A PVB goes at least 12 inches above them. An RP and a DC go horizontal unless listed otherwise. An AVB can't have a shutoff valve downstream and can't be under constant pressure. Assemblies that can discharge, such as an RP or a PVB, need a drain or a spot where spill water won't hurt anything.

Lawn sprinklers and irrigation

A sprinkler system is a cross-connection by nature. The pipes sit in the ground with fertilizer, pesticides and standing water around the heads. Which device you use depends on what the system has. The simple case is no pump, no connection for pumping equipment, and no chemical injection. A pump, an auxiliary air tank or anything else that can create backpressure calls for an RP located upstream of the source. Chemical injection also calls for an RP (CPC 603.5.6). Ask early whether there's a pump, a booster, a rainwater tie-in or a fertilizer injector. The answer decides the device. Mounting a PVB low is the most common correction, because it has to sit at least 12 inches above the highest downstream piping.

Hose bibbs

Every outdoor faucet that takes a hose needs a nonremovable hose-bibb backflow preventer or vacuum breaker, or an atmospheric vacuum breaker at least 6 inches above the highest point of use on the discharge side of the last valve. Water heater drains, boiler drains and clothes washer connections are excepted. In freezing climates, use a listed self-draining frost-proof bibb with a built-in breaker (CPC 603.5.7). Many bibbs ship with the vent cap already on. Leave it on.

Testing and access

A device has to be approved by the building department before it goes in. It's tested when installed, repaired or moved, and then at least once a year, or more often if the department requires. A failed device is repaired or replaced, and testing is done by a certified backflow tester or repairer (CPC 603.2). Your local water supplier may run its own cross-connection program and ask for more, so call them before you buy an assembly.

A testable assembly needs room. Leave at least 12 inches between the bottom of the assembly and the grade, floor or platform, with access per the manufacturer's instructions. If it's mounted more than 5 feet up, it needs a platform that can hold a person (CPC 603.4.3). A device boxed into a shrub bed can't be tested.

What you can safely check yourself

Look at your outdoor faucets for a small cap or vent on the spout, and leave it alone. Don't leave a hose submerged in a pool, bucket, tub or chemical sprayer. If you have a sprinkler backflow assembly, check that it stands upright, that the area around it is clear, and that you have a test tag or record with a date. Don't open the test cocks, adjust a device, or shut off the supply to an assembly without knowing how.

Questions

How often does a backflow assembly need testing?

At installation, after repair or relocation, and at least once a year (CPC 603.2).

Who can test a backflow assembly?

A certified backflow assembly tester or repairer, or another certification the building department accepts (CPC 603.2).

Do I need an RP for my sprinkler system?

Only if the system has a pump, a connection for pumping equipment, an air tank or chemical injection. Otherwise the code has several simpler options (CPC 603.5.6).

Why does my outdoor faucet have a little cap on it?

That's the vacuum breaker vent. It keeps a hose from siphoning back into the house (CPC 603.5.7).

When to call

The annual test is done by a certified tester, and installation needs the building department's approval and often the water supplier's too. For the water supply piping around a device, call or text (760) 912-9831. "Water line repairs" and "Shut-off valve replacement" are on our service and repair list, and "Water and sewer lines" is on our new construction list.