Sewer backups, cleanouts and backwater valves

When the lowest drains in the house back up first, the problem is usually in the main line or the sewer, and a cleanout is where a plumber gets at it. Fixtures below the street manhole need a backwater valve.

The short answer

Wastewater looks for the lowest opening. A backup that shows first in a basement bath, a garage floor drain or a ground-floor shower is the classic sign of a blocked or slow main line. Every horizontal drain is supposed to have a cleanout at its upper end and another for each 100 feet of run (CPC 707.0), and a main cleanout where the building drain meets the sewer (CPC 719.1). If any fixture sits lower than the next upstream manhole cover on the public or private sewer, the code requires an approved backwater valve to protect it (CPC 710.1).

Do this first

Stop running water. Don't use the fixtures that drain to the backed-up line, and don't open a cleanout on a line that's backed up. Then call a plumber.

Why the lowest fixtures go first

Gravity drains need slope. A building drain and its horizontal branches run at a uniform slope of at least 1/4 inch per foot (CPC 708.1), and the building sewer follows the same 1/4 inch per foot baseline (CPC 718.1). Where depth or layout make that impractical, a larger pipe can go flatter, but only with the building department's approval ahead of time. Flatter pipe carries less.

When something blocks the line, the water has nowhere to go and finds the first opening below the blockage: a tub, a floor drain, a toilet. In older houses a belly or a root intrusion in the sewer is a common cause. A slow drain on the lowest level, or gurgling when upstairs fixtures run, is the early warning. A camera scope shows what the line looks like.

Where cleanouts are required

Section 707.4 puts a cleanout at the upper end of every horizontal drain, one more for each 100 feet of run, and one for each aggregate horizontal change of direction over 135 degrees. Short runs under 5 feet are excepted unless they serve sinks or urinals (CPC 707.0).

The building sewer gets its own: either inside near the point where the building drain meets the sewer, or outside at the lower end of the building drain, extended to grade. More go on the sewer at intervals of 100 feet or less in straight runs and at each aggregate turn over 135 degrees (CPC 719.1). A two-way cleanout near the foundation is common and lets a plumber clean in both directions.

A cleanout has to be reachable. Above grade or under a cover plate, with 18 by 18 inches of clear space in front of it on pipe 2 inches or smaller, and 24 by 24 inches on larger pipe. Under a floor, an under-floor cleanout can't be more than 5 feet from the access opening (CPC 707.8).

Backwater valves

When the street sewer backs up, wastewater rises to the level of the next upstream manhole cover before it spills there. Any fixture on a floor lower than that cover, such as a basement bath, a garage drain or a lower-level laundry, can be flooded from its own drain. Those fixtures need an approved backwater valve. Fixtures on higher floors have to be piped so they don't discharge through the valve, which keeps the rest of the house working if the valve closes. Cleanouts on the line behind the valve carry a permanent label that reads "backwater valve downstream" (CPC 710.1).

A valve has to be reachable for inspection and cleaning, in a masonry pit with a removable cover unless it's continuously exposed (CPC 710.6). Burying one with no access is a common correction and a hard fix. To know whether your house needs one, compare the manhole cover elevation from the city or sewer district to the floor level of your lowest fixture.

Sewage ejectors for below-sewer fixtures

Where a fixture is below the sewer, a sewage ejector can lift waste from a sealed basin. For a single dwelling, the pump has to move at least 20 gpm and pass a 1-1/2 inch solid ball, with a discharge line of at least 2 inches. The discharge line gets a backwater valve and a gate valve (CPC 710.3). A lidded basin in a basement floor is usually one. If the alarm sounds or the pump runs constantly, it's a call.

What you can safely check yourself

Find your cleanouts. They look like a capped round or square plug on a short pipe, often outside near the house, in a garage floor or under a cover plate. Keep the 18 to 24 inch space in front of them clear of stored items and landscaping, and tell your plumber where they are. If you have a backwater valve, look for the access cover and the "backwater valve downstream" label. Leave all caps and covers in place during a backup. Opening one on a backed-up line can flood the space with sewage. Don't pour drain chemicals into a slow main line.

Questions

Does clearing a stoppage need a permit?

Usually not. Clearing stoppages, including pulling and resetting a toilet, is exempt from a plumbing permit. Replacing a defective trap or a section of drain pipe is new work and does need one (CPC 104.2). Ask your building department.

How often should a sewer line be cleaned?

The code doesn't set a schedule. Slow drains, gurgling and repeated backups in the lowest fixtures are the signs to act on.

Do I need a backwater valve?

If a fixture sits below the next upstream manhole cover, yes (CPC 710.1). Get the manhole elevation from your sewer agency and compare it to your lowest floor.

Does a detached building share my sewer connection?

Each building gets its own connection to the public or private sewer where one's available, with limited exceptions. See our ADU plumbing guide. The inspector and your city's adopted edition of the code have the final word.

When to call

If drains are backing up, gurgling or slow in the lowest part of the house, call or text (760) 912-9831. "Drain & sewer issues" is on our service and repair list, and "Water and sewer lines" is on our new construction list for new cleanouts, backwater valves and building sewers.